The vendor explicitly identifies these products as affected by this CVE.
- SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)
- SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)
- SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0)
- SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)
- SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0)
- SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
- SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0)
- SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0)
- SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0)
- SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)
- SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)
- SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)
- Summary
- Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
- Remediation
- Update to V1.3 or later version