Evidence used
- No CISA KEV confirmation is currently recorded.
- EPSS is 0.26% for the current model date.
BlackTreeCVE IntelligenceSiemens · MS/TP Point Pickup Module
Official source article: Siemens SSA-668154 ↗. Check the applicable product and release in the original source.
High technical severity; prioritise exposed affected systems while verifying vendor guidance.
Structured product status and remediation from the issuing vendor. Product-state explanations are always visible; large lists can be searched or downloaded.
The vendor explicitly identifies these products as affected by this CVE.
High technical severity; prioritise exposed affected systems while verifying vendor guidance.
Fix not verifiedA vulnerability has been identified in MS/TP Point Pickup Module (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the same BACnet network to send a specially crafted MSTP message that results in a denial of service condition of the targeted device. A power cycle is required to restore the device's normal operation.
A vulnerability has been identified in MS/TP Point Pickup Module (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the same BACnet network to send a specially crafted MSTP message that results in a denial of service condition of the targeted device. A power cycle is required to restore the device's normal operation.
The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.
An attacker operating through an adjacent network may attempt exploitation without authentication or user interaction. If successful, the issue may disrupt the affected service.
A vulnerability has been identified in MS/TP Point Pickup Module (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the same BACnet network to send a specially crafted MSTP message that results in a denial of service condition of the targeted device. A power cycle is required to restore the device's normal operation.
The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.
An attacker operating through an adjacent network may attempt exploitation without authentication or user interaction. If successful, the issue may disrupt the affected service.
CVSS severity, EPSS forecast probability, public exploit material and CISA-confirmed exploitation are separate signals.
No CISA KEV match was present at the last successful refresh. This means no confirmation from that source, not proof of no exploitation.
No exploit-tagged reference or CISA SSVC proof-of-concept state is currently recorded. Research may still exist outside the structured feeds.
CWE-20: Improper Input Validation. The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:NCommon Vulnerability Scoring System 4.0: the compact vector below is decoded into plain language.
Operational remediation based on structured source evidence.
Published 13 May 2025 · Last source change 13 May 2025, 19:00 UTC · CWE-20 · Improper Input Validation
Core structured fields are present and their contributing authorities are shown above.
No material field changes have been recorded since change tracking began. Routine source refreshes and cosmetic edits are intentionally excluded.